At 12:41 EST a utility fault, occurring between our transformer and main disconnect, caused phase B of the main power feed for DC3 to be interrupted. As a result our ATS transferred power to our generator until which time we were on our generator until approximately 13:15 EST. At this time our ATS read a severe fault and and went into EPO, we suspect as a result of the initial issue which caused phase B to fail at our main disconnect. Local service technicians from the utility provider and our equipment vendors were on-site and working on resolving the problem immediately.
Taking into consideration the original problem it was decided to bypass our main disconnect, ATS and primary generator in case there were any residual issues yet to be observed.
At approximately 19:00 EST power was restored to the building and circuits were systematically brought up and individually assessed to be in optimal working condition. During this process, some of you will have found your services to be active before others.
All services should have been restored by approximately 19:55 EST. If are still experiencing any issues please direct your email to [email protected] or your browser to https://support.carohosting.com/ and we will assist you promptly.
As always we appreciate your patronage and your patience while we were forced to deal with the unfortunate circumstances.
As yet another unfortunate turn of events, the temporary generator we were using to supply power to DC3 caught fire at approximately 03:00 EST this morning. As a result of the fire we were forced to EPO DC3 by order of the Mecklenburg County Fire Marshall.
Shortly after the fire began we requested a “replacement, replacement” generator from our vendor knowing the likely outcome of these events. Once the fire department had completely put out the fire it was determined that the generator was all but a complete loss and was of no further use to us.
Due to delays outside of our control it took roughly four more hours for the “replacement, replacement” generator to be on site and we had it connected and supplying power in just under 30 minutes.
At this time all service should be restored and we’re vigilantly monitoring the situation to ensure there are no further interruptions.
Considering the unbelievable nature of the past 24 hours, pictures of some of the events will be forth coming and we will be providing links to these photo sets within this RFO.